Startup and the global governor
Startup is a conversation, not one state machine. The dashboard reports what the driver is asking for; the front controller decides whether to act; the accumulator, inverters and LV controller do the physical work.
| Layer | Responsibility |
|---|---|
| Dashboard | Shows prompts and sends the driver's requested next step in DashStatus |
| Front controller governor | Owns the overall startup state and decides when HV, motors and torque are allowed |
| FC accumulator | Sequences the three contactors and monitors feedback |
| FC motors | Runs the two AMK inverter startup sequences |
| LV controller | Powers the ECUs, accumulator electronics and inverter supply; closes the shared inverter switch |
| TMS | Reports temperatures; not part of the startup handshake |
Global governor
This is the front controller's top-level state machine. It is the single source of truth for whether the car is allowed to drive.
stateDiagram-v2
[*] --> START_DASHBOARD
START_DASHBOARD --> WAIT_DRIVER_SELECT: Dash LOGO or SELECT_PROFILE
WAIT_DRIVER_SELECT --> WAIT_START_HV: Dash WAIT_SELECTION_ACK
WAIT_START_HV --> STARTING_HV: Dash STARTING_HV
STARTING_HV --> WAIT_START_MOTOR: Accumulator RUNNING
STARTING_HV --> ERROR: Accumulator ERROR
WAIT_START_MOTOR --> STARTING_MOTORS: Dash STARTING_MOTORS
STARTING_MOTORS --> STARTUP_SEND_READY_TO_DRIVE: Motors RUNNING
STARTING_MOTORS --> ERROR: Motors ERROR
STARTUP_SEND_READY_TO_DRIVE --> RUNNING: FC brake > 10%
RUNNING --> ERROR: Accumulator or motors ERROR
RUNNING --> SHUTDOWN: Dash SHUTDOWN
ERROR --> SHUTDOWN: Dash SHUTDOWN
SHUTDOWN --> START_DASHBOARD: Accumulator IDLE
State numbers come from FcStatus.State in veh.dbc. Value 1 is unused.
| State | Value | FC outputs | Advances when | Fault behavior |
|---|---|---|---|---|
START_DASHBOARD |
0 | Accumulator OFF, motors OFF, torque 0 | Dashboard reports LOGO or SELECT_PROFILE |
After 10 s, sets DashboardBootTimeout alert but keeps waiting |
WAIT_DRIVER_SELECT |
2 | OFF, OFF, torque 0 | Dashboard reports WAIT_SELECTION_ACK; profile is stored |
No timeout |
WAIT_START_HV |
3 | OFF, OFF, torque 0 | Dashboard reports STARTING_HV |
No timeout |
STARTING_HV |
4 | Accumulator ENABLED, motors OFF, torque 0 | Accumulator reaches RUNNING |
Accumulator ERROR → ERROR |
WAIT_START_MOTOR |
5 | Accumulator ENABLED, motors OFF, torque 0 | Dashboard reports STARTING_MOTORS |
Does not check accumulator error here |
STARTING_MOTORS |
6 | Both ENABLED, torque 0 | Motors reach RUNNING |
Motors ERROR → ERROR; does not check accumulator error here |
STARTUP_SEND_READY_TO_DRIVE |
7 | Both ENABLED, torque 0 | FC's own brake reading is above 10% | No timeout and no subsystem-error check |
RUNNING |
8 | Both ENABLED, driver torque allowed | Stays until error or shutdown | Accumulator/motor ERROR → ERROR; dashboard SHUTDOWN → SHUTDOWN |
SHUTDOWN |
9 | OFF, OFF, torque 0 | Accumulator reaches IDLE |
Waits for the accumulator only |
ERROR |
10 | OFF, OFF, torque 0 | Dashboard reports SHUTDOWN |
No automatic recovery |
The ready-to-drive speaker turns on after entering RUNNING and stays on for
about 2 seconds. Torque is not held at zero during that time.
The interlock branch is inactive
There is a local hvil_interrupt check after the governor switch, but the
variable is always false in this revision. It creates no transition. The
physical shutdown circuit is separate from this software path.
Driver and dashboard handshake
sequenceDiagram
autonumber
actor Driver
participant Dash as Dashboard
participant FC as Front controller
participant Acc as FC accumulator
participant Motors as FC motors
participant LV as LV controller
Driver->>Dash: Select profile and confirm
Dash->>FC: DashStatus = WAIT_SELECTION_ACK + profile
FC->>FC: WAIT_DRIVER_SELECT → WAIT_START_HV
FC-->>Dash: DashCommand.ConfigReceived = true
Driver->>Dash: ENTER at "press for HV"
Dash->>FC: DashStatus = STARTING_HV
FC->>Acc: ENABLED
Acc-->>FC: accumulator RUNNING
FC->>FC: STARTING_HV → WAIT_START_MOTOR
FC-->>Dash: DashCommand.HvStarted = true
Driver->>Dash: ENTER with brake pressed
Dash->>FC: DashStatus = STARTING_MOTORS
FC->>Motors: ENABLED
FC->>LV: InverterSwitchCommand.CloseInverterSwitch
LV-->>FC: LvStatus.MotorControllerSwitchClosed
Motors-->>FC: motors RUNNING
FC->>FC: STARTING_MOTORS → STARTUP_SEND_READY_TO_DRIVE
FC-->>Dash: DashCommand.MotorStarted = true
Driver->>FC: Brake pedal above 10%
FC->>FC: STARTUP_SEND_READY_TO_DRIVE → RUNNING
FC-->>Dash: DashCommand.DriveStarted = true
DashCommand is a set of repeated level bits, not one-shot events:
| Bit | True when |
|---|---|
ConfigReceived |
FC governor is in WAIT_START_HV |
HvStarted |
Accumulator is RUNNING |
MotorStarted |
Motor coordinator is RUNNING |
DriveStarted |
FC governor is in RUNNING |
Reset |
FC governor is in START_DASHBOARD |
Errored |
FC governor is in ERROR |
HvShutdown |
FC governor is in SHUTDOWN |
Dashboard state machine
The dashboard's screen state is the driver's request. It is sent over CAN every loop, including while driving.
stateDiagram-v2
[*] --> SELECT_PROFILE
SELECT_PROFILE --> CONFIRM_SELECTION: ENTER
CONFIRM_SELECTION --> SELECT_PROFILE: CHANGE, then ENTER
CONFIRM_SELECTION --> WAIT_SELECTION_ACK: CONFIRM, then ENTER
WAIT_SELECTION_ACK --> PRESS_FOR_HV: ConfigReceived
PRESS_FOR_HV --> STARTING_HV: ENTER
STARTING_HV --> PRESS_FOR_MOTOR: HvStarted
PRESS_FOR_MOTOR --> STARTING_MOTORS: ENTER + brake > 0.20
STARTING_MOTORS --> BRAKE_TO_START: MotorStarted
BRAKE_TO_START --> RUNNING: DriveStarted
ERROR --> SHUTDOWN: ENTER held > 3000 ms
SHUTDOWN --> SELECT_PROFILE: Reset
RUNNING --> SELECT_PROFILE: Reset
LOGO exists in the DBC but is never selected by the dashboard, which boots
directly into SELECT_PROFILE.
Global Reset: after the active screen updates, Display::Update() checks
DashCommand.Reset. If it is true and the dashboard is not already in
SELECT_PROFILE, it forces SELECT_PROFILE.
The error and shutdown screens are incomplete
No normal screen transition enters ERROR, and the running screen has no
shutdown action. The FC sends DashCommand.Errored and HvShutdown, but
the dashboard does not consume either bit. The error screen's
hold-ENTER-to-shutdown path is therefore not reachable through the normal
driver flow.
What happens underneath
The governor only requests; two FC modules do the physical work:
- Accumulator: ensure all contactors open, close negative, close precharge, wait for more than 90% and at least 10 s, close positive, then open precharge. Contactor feedback is inverted, and a wrong or missing state can fault or stall the sequence.
- Motors: start both AMK inverters. When both reach the X140 handoff, the FC
asks the LV controller to close the shared inverter switch. The LV reports its
requested switch state, and the motors enter
RUNNING.
See Front controller for the detailed state diagrams and fault paths.
Timing
| Context | Nominal period | Startup-relevant work |
|---|---|---|
| FC control task | 10 ms (100 Hz) | Sensors, governor, accumulator, dynamics, motors, commands |
| FC status task | 100 ms (10 Hz) | FcStatus, DashCommand, alerts, diagnostics |
| FC identity task | 1000 ms (1 Hz) | Git revision |
| Dashboard loop | 20 ms delay + work | Buttons, active screen, DashStatus |
| LV tasks | 10 / 100 / 1000 ms intended | Governor, modules, status (see the LV scheduler note) |
| TMS tasks | 100 / 1000 ms | Temperature reporting, fan-duty calculation, Git revision |
Key delays and thresholds:
| Item | Value |
|---|---|
| Minimum precharge time | 10 s |
| Precharge complete | > 90% of pack voltage |
| Contactor step hold | 100 ms |
| Pack voltage data timeout | 500 ms |
| Shutdown discharge complete | < 10% after > 5 s |
| FC brake-to-drive threshold | > 10% |
| Dashboard brake-to-start threshold | > 0.20 percentage points |
| Dashboard boot alert | > 10 s |
| Ready-to-drive speaker | ~2 s |
The FC's elapsed counters are software counters incremented by 10 per 100 Hz
update. They are not wall-clock deadlines, and a late task does not change the
increment.
Most governor waits have no timeout. If the dashboard stops sending, its last
DashStatus remains valid and can still drive a transition because there is no
sender-age check. Missing contactor feedback or a missing LvStatus likewise
leaves the relevant state machine waiting. The pack-voltage check is the main
exception at 500 ms.
Shutdown and restart
A dashboard SHUTDOWN request is accepted in RUNNING and ERROR. The FC then:
- commands the accumulator and motors OFF;
- the accumulator opens all three contactors;
- the accumulator waits for precharge below 10% and more than 5 seconds, then
reports
IDLE; - the FC returns to
START_DASHBOARD.
DashCommand.Reset is true while the FC is in START_DASHBOARD, so the
dashboard returns to profile selection. The dashboard remains powered
throughout; its power is controlled by the FC GPIO, not by this state machine.
The physical shutdown circuit can remove power independently of any of these software states. This repository documents the software requests and feedback it can observe, not the complete electrical response of that circuit.