Startup and the global governor

Startup is a conversation, not one state machine. The dashboard reports what the driver is asking for; the front controller decides whether to act; the accumulator, inverters and LV controller do the physical work.

Layer Responsibility
Dashboard Shows prompts and sends the driver's requested next step in DashStatus
Front controller governor Owns the overall startup state and decides when HV, motors and torque are allowed
FC accumulator Sequences the three contactors and monitors feedback
FC motors Runs the two AMK inverter startup sequences
LV controller Powers the ECUs, accumulator electronics and inverter supply; closes the shared inverter switch
TMS Reports temperatures; not part of the startup handshake

Global governor

This is the front controller's top-level state machine. It is the single source of truth for whether the car is allowed to drive.

stateDiagram-v2
    [*] --> START_DASHBOARD
    START_DASHBOARD --> WAIT_DRIVER_SELECT: Dash LOGO or SELECT_PROFILE
    WAIT_DRIVER_SELECT --> WAIT_START_HV: Dash WAIT_SELECTION_ACK
    WAIT_START_HV --> STARTING_HV: Dash STARTING_HV
    STARTING_HV --> WAIT_START_MOTOR: Accumulator RUNNING
    STARTING_HV --> ERROR: Accumulator ERROR
    WAIT_START_MOTOR --> STARTING_MOTORS: Dash STARTING_MOTORS
    STARTING_MOTORS --> STARTUP_SEND_READY_TO_DRIVE: Motors RUNNING
    STARTING_MOTORS --> ERROR: Motors ERROR
    STARTUP_SEND_READY_TO_DRIVE --> RUNNING: FC brake > 10%
    RUNNING --> ERROR: Accumulator or motors ERROR
    RUNNING --> SHUTDOWN: Dash SHUTDOWN
    ERROR --> SHUTDOWN: Dash SHUTDOWN
    SHUTDOWN --> START_DASHBOARD: Accumulator IDLE

State numbers come from FcStatus.State in veh.dbc. Value 1 is unused.

State Value FC outputs Advances when Fault behavior
START_DASHBOARD 0 Accumulator OFF, motors OFF, torque 0 Dashboard reports LOGO or SELECT_PROFILE After 10 s, sets DashboardBootTimeout alert but keeps waiting
WAIT_DRIVER_SELECT 2 OFF, OFF, torque 0 Dashboard reports WAIT_SELECTION_ACK; profile is stored No timeout
WAIT_START_HV 3 OFF, OFF, torque 0 Dashboard reports STARTING_HV No timeout
STARTING_HV 4 Accumulator ENABLED, motors OFF, torque 0 Accumulator reaches RUNNING Accumulator ERROR → ERROR
WAIT_START_MOTOR 5 Accumulator ENABLED, motors OFF, torque 0 Dashboard reports STARTING_MOTORS Does not check accumulator error here
STARTING_MOTORS 6 Both ENABLED, torque 0 Motors reach RUNNING Motors ERROR → ERROR; does not check accumulator error here
STARTUP_SEND_READY_TO_DRIVE 7 Both ENABLED, torque 0 FC's own brake reading is above 10% No timeout and no subsystem-error check
RUNNING 8 Both ENABLED, driver torque allowed Stays until error or shutdown Accumulator/motor ERROR → ERROR; dashboard SHUTDOWN → SHUTDOWN
SHUTDOWN 9 OFF, OFF, torque 0 Accumulator reaches IDLE Waits for the accumulator only
ERROR 10 OFF, OFF, torque 0 Dashboard reports SHUTDOWN No automatic recovery

The ready-to-drive speaker turns on after entering RUNNING and stays on for about 2 seconds. Torque is not held at zero during that time.

The interlock branch is inactive

There is a local hvil_interrupt check after the governor switch, but the variable is always false in this revision. It creates no transition. The physical shutdown circuit is separate from this software path.

Driver and dashboard handshake

sequenceDiagram
    autonumber
    actor Driver
    participant Dash as Dashboard
    participant FC as Front controller
    participant Acc as FC accumulator
    participant Motors as FC motors
    participant LV as LV controller

    Driver->>Dash: Select profile and confirm
    Dash->>FC: DashStatus = WAIT_SELECTION_ACK + profile
    FC->>FC: WAIT_DRIVER_SELECT → WAIT_START_HV
    FC-->>Dash: DashCommand.ConfigReceived = true

    Driver->>Dash: ENTER at "press for HV"
    Dash->>FC: DashStatus = STARTING_HV
    FC->>Acc: ENABLED
    Acc-->>FC: accumulator RUNNING
    FC->>FC: STARTING_HV → WAIT_START_MOTOR
    FC-->>Dash: DashCommand.HvStarted = true

    Driver->>Dash: ENTER with brake pressed
    Dash->>FC: DashStatus = STARTING_MOTORS
    FC->>Motors: ENABLED
    FC->>LV: InverterSwitchCommand.CloseInverterSwitch
    LV-->>FC: LvStatus.MotorControllerSwitchClosed
    Motors-->>FC: motors RUNNING
    FC->>FC: STARTING_MOTORS → STARTUP_SEND_READY_TO_DRIVE
    FC-->>Dash: DashCommand.MotorStarted = true

    Driver->>FC: Brake pedal above 10%
    FC->>FC: STARTUP_SEND_READY_TO_DRIVE → RUNNING
    FC-->>Dash: DashCommand.DriveStarted = true

DashCommand is a set of repeated level bits, not one-shot events:

Bit True when
ConfigReceived FC governor is in WAIT_START_HV
HvStarted Accumulator is RUNNING
MotorStarted Motor coordinator is RUNNING
DriveStarted FC governor is in RUNNING
Reset FC governor is in START_DASHBOARD
Errored FC governor is in ERROR
HvShutdown FC governor is in SHUTDOWN

Dashboard state machine

The dashboard's screen state is the driver's request. It is sent over CAN every loop, including while driving.

stateDiagram-v2
    [*] --> SELECT_PROFILE
    SELECT_PROFILE --> CONFIRM_SELECTION: ENTER
    CONFIRM_SELECTION --> SELECT_PROFILE: CHANGE, then ENTER
    CONFIRM_SELECTION --> WAIT_SELECTION_ACK: CONFIRM, then ENTER
    WAIT_SELECTION_ACK --> PRESS_FOR_HV: ConfigReceived
    PRESS_FOR_HV --> STARTING_HV: ENTER
    STARTING_HV --> PRESS_FOR_MOTOR: HvStarted
    PRESS_FOR_MOTOR --> STARTING_MOTORS: ENTER + brake > 0.20
    STARTING_MOTORS --> BRAKE_TO_START: MotorStarted
    BRAKE_TO_START --> RUNNING: DriveStarted
    ERROR --> SHUTDOWN: ENTER held > 3000 ms
    SHUTDOWN --> SELECT_PROFILE: Reset
    RUNNING --> SELECT_PROFILE: Reset

LOGO exists in the DBC but is never selected by the dashboard, which boots directly into SELECT_PROFILE.

Global Reset: after the active screen updates, Display::Update() checks DashCommand.Reset. If it is true and the dashboard is not already in SELECT_PROFILE, it forces SELECT_PROFILE.

The error and shutdown screens are incomplete

No normal screen transition enters ERROR, and the running screen has no shutdown action. The FC sends DashCommand.Errored and HvShutdown, but the dashboard does not consume either bit. The error screen's hold-ENTER-to-shutdown path is therefore not reachable through the normal driver flow.

What happens underneath

The governor only requests; two FC modules do the physical work:

  • Accumulator: ensure all contactors open, close negative, close precharge, wait for more than 90% and at least 10 s, close positive, then open precharge. Contactor feedback is inverted, and a wrong or missing state can fault or stall the sequence.
  • Motors: start both AMK inverters. When both reach the X140 handoff, the FC asks the LV controller to close the shared inverter switch. The LV reports its requested switch state, and the motors enter RUNNING.

See Front controller for the detailed state diagrams and fault paths.

Timing

Context Nominal period Startup-relevant work
FC control task 10 ms (100 Hz) Sensors, governor, accumulator, dynamics, motors, commands
FC status task 100 ms (10 Hz) FcStatus, DashCommand, alerts, diagnostics
FC identity task 1000 ms (1 Hz) Git revision
Dashboard loop 20 ms delay + work Buttons, active screen, DashStatus
LV tasks 10 / 100 / 1000 ms intended Governor, modules, status (see the LV scheduler note)
TMS tasks 100 / 1000 ms Temperature reporting, fan-duty calculation, Git revision

Key delays and thresholds:

Item Value
Minimum precharge time 10 s
Precharge complete > 90% of pack voltage
Contactor step hold 100 ms
Pack voltage data timeout 500 ms
Shutdown discharge complete < 10% after > 5 s
FC brake-to-drive threshold > 10%
Dashboard brake-to-start threshold > 0.20 percentage points
Dashboard boot alert > 10 s
Ready-to-drive speaker ~2 s

The FC's elapsed counters are software counters incremented by 10 per 100 Hz update. They are not wall-clock deadlines, and a late task does not change the increment.

Most governor waits have no timeout. If the dashboard stops sending, its last DashStatus remains valid and can still drive a transition because there is no sender-age check. Missing contactor feedback or a missing LvStatus likewise leaves the relevant state machine waiting. The pack-voltage check is the main exception at 500 ms.

Shutdown and restart

A dashboard SHUTDOWN request is accepted in RUNNING and ERROR. The FC then:

  1. commands the accumulator and motors OFF;
  2. the accumulator opens all three contactors;
  3. the accumulator waits for precharge below 10% and more than 5 seconds, then reports IDLE;
  4. the FC returns to START_DASHBOARD.

DashCommand.Reset is true while the FC is in START_DASHBOARD, so the dashboard returns to profile selection. The dashboard remains powered throughout; its power is controlled by the FC GPIO, not by this state machine.

The physical shutdown circuit can remove power independently of any of these software states. This repository documents the software requests and feedback it can observe, not the complete electrical response of that circuit.